Introduction
Damage from electrical transients, or surges, is
one of the leading causes of electrical equipment failure. An electrical
transient is a short duration, high-energy impulse that is imparted on
the normal electrical power system whenever there is a sudden change in
the electrical circuit. They can originate from a variety of sources,
both internal and external to a facility.
Not
Just Lightning
The most obvious source is from lightning, but
surges can also come from normal utility switching operations, or
unintentional grounding of electrical conductors (such as when an
overhead power line falls to the ground). Surges may even come from
within a building or facility from such things as fax machines, copiers,
air conditioners, elevators, motors/pumps, or arc welders, to name a
few. In each case, the normal electric circuit is suddenly exposed to a
large dose of energy that can adversely affect the equipment being
supplied power.
The following is a guideline on how to protect
electrical equipment from the devastating effects of high-energy surges.
Surge protection that is properly sized and installed is highly
successful in preventing equipment damage, especially for sensitive
electronic equipment found in most equipment today.
Grounding
Is Fundamental
A surge protection device (SPD), also known as a
transient voltage surge suppressor (TVSS), is designed to divert
high-current surges to ground and bypass your equipment, thereby
limiting the voltage that is impressed on the equipment. For this
reason, it is critical that your facility have a good, low-resistance
grounding system, with a single ground reference point to which the
grounds of all building systems are connected. Without a proper
grounding system, there is no way to protect against surges. Consult
with a licensed electrician to ensure that your electrical distribution
system is grounded in accordance with the National Electric Code (NFPA
70).
Zones Of
Protection
The best means of protecting your electrical
equipment from high-energy electrical surges is to install SPDs
strategically throughout your facility. Considering that surges can
originate from both internal and external sources, SPDs should be
installed to provide maximum protection regardless of the source
location. For this reason, a "Zone of Protection" approach is generally
employed. The first level of defense is achieved by installing an SPD on
the main service entrance equipment (i.e., where the utility power comes
into the facility). This will provide protection against high energy
surges coming in from the outside, such as lightning or utility
transients.
However, the SPD installed at the service entrance
will not protect against internally generated surges. In addition, not
all of the energy from outside surges is dissipated to ground by the
service entrance device. For this reason, SPDs should be installed on
all distribution panels within a facility that supply power to critical
equipment. Similarly, a third zone of protection would be achieved by
installing SPDs locally for each piece of equipment being protected,
such as computers or computer controlled devices. Each zone of
protection adds to the overall protection of the facility as each helps
to further reduce the voltage exposed to the protected equipment.
Coordination of SPDs
The service entrance SPD provides the first line
of defense against electrical transients for a facility by diverting
high-energy, outside surges to ground. It also lowers the energy level
of the surge entering the facility to a level that can be handled by
downstream devices closer to the load. Therefore, proper coordination of
SPDs is required to avoid damaging SPDs installed on distribution panels
or locally at vulnerable equipment. If coordination is not achieved,
excess energy from propagating surges can cause damage to Zone 2 and
Zone 3 SPDs and destroy the equipment that you are trying to protect.
SPD
Ratings
When selecting an SPD for a given application,
there are several considerations that must be made:
-
Application - Ensure that the SPD is designed for
the zone of protection for which it will be used. For example, an
SPD at the service entrance should be designed to handle the larger
surges that result from lightning or utility switching.
-
System voltage and configuration - SPDs are
designed for specific voltage levels and circuit configurations. For
example, your service entrance equipment may be supplied three phase
power at 480/277 V in a four-wire wye connection, but a local
computer is installed to a single-phase, 120 V supply.
-
Let-through voltage - This is the voltage that the
SPD will allow the protected equipment to be exposed to. However,
the potential damage to equipment is dependent on how long the
equipment is exposed to this let-through voltage in relation to the
equipment design. In other words, equipment is generally designed to
withstand a high voltage for a very short period of time, and lower
voltage surges for a longer period of time. The Federal Information
Processing Standards (FIPS) publication "Guideline on Electrical
Power for Automatic Data Processing Installations" (FIPS Pub. DU294)
provides details on the relationship between clamping voltage,
system voltage, and surge duration.
As an example, a transient on a 480 V line that lasts for 20
microseconds can rise to almost 3400V without damaging equipment
designed to this guideline. But a surge around 2300 V could be
sustained for 100 microseconds without causing damage. Generally
speaking, the lower the clamp voltage, the better the protection.
Surge current - SPDs are rated to safely divert a given amount of
surge current without failing. This rating ranges from a few
thousand amps up to 400 kiloamperes (kA) or more. However, the
average current of a lightning strike is only approximately 20 kA.,
with the highest measured currents being just over 200 kA. Lightning
that strikes a power line will travel in both directions, so only
half the current travels toward your facility. Along the way, some
of the current may dissipate to ground through utility equipment.
Therefore, the potential current at the service entrance from an
average lightning strike is somewhere around 10 kA. In addition,
certain areas of the country are more prone to lightning strikes
than others. All of these factors must be considered when deciding
what size SPD is appropriate for your application.
However, it is important to consider that an SPD rated at 20 kA may
be sufficient to protect against the average lightning strike and
most internally generated surges once, but an SPD that is rated 100
kA will be able to handle additional surges without having to
replace the arrester or fuses.
Standards - All SPDs should be tested in accordance with ANSI/IEEE
C62.41 and be listed to UL 1449 (2nd Edition) for safety.
Data Line
Protection
Electrical transients are not confined to the
electrical distribution system. They can enter a facility through
phone/fax lines, cable or satellite systems, and local area networks
(LAN). Therefore, in order to achieve maximum protection from surge
damage, SPDs should be installed on all systems susceptible to
electrical transients.
Installation
For maximum protection, SPDs should be installed
as close to the equipment being protected as possible. Cable lengths
should be as short and straight as possible to minimize the resistive
path of the circuit to ground. A solid connection to the system
grounding conductor is essential for proper operation of the SPDs. The
surge protectors should be equipped with indicators that show if the
circuit is grounded and operating properly, and the units installed so
these indicators can be easily inspected.
All service entrance and distribution panel SPDs
should only be installed by a licensed electrician familiar with the
equipment and its use. In addition,
2 Wire Electric Inc.
strongly recommends that a professional engineer
experienced with surge suppression technology be retained to design the
protection scheme for your facility to ensure all SPDs are properly
sized and coordinated.
Residential
Top
|